Strany 1 - PowerSeries

PowerSeries PC1616/PC1832/PC1864 version 4.2 EUInstallation GuideWARNING: This manual contains information on limitations regarding product use and fu

Strany 2 - Table of Contents

PowerSeries - PC1616/PC1832/PC18648[][6] – User FunctionsPress [][6] followed by the Master Code, then press the number corresponding to the followi

Strany 3

Section 4: Programming9Section 4: ProgrammingThis section provides the information necessary to program all required features for a basic system as we

Strany 4 - Installation

PowerSeries - PC1616/PC1832/PC1864104.5 Viewing ProgrammingLED and LCD5501Z KeypadsLCD KeypadThe keypad will immediately display all the information

Strany 5 - Burglary Zone Wiring Chart

Section 5 – Programming Descriptions11Section 5 – Programming DescriptionsThe following is a brief description of the features and options available i

Strany 6 - PC1616/1832/1864

PowerSeries - PC1616/PC1832/PC186412Section [005] System TimesAfter entering Section [005], enter the 2-digit subsection number for the desired partit

Strany 7 - AC Wiring

Section 5 – Programming Descriptions13Section [012] Keypad LockoutThe system can be programmed to ‘lockout’ keypads if a series of incorrect user or i

Strany 8 - Section 3: User Commands

PowerSeries - PC1616/PC1832/PC186414[014] Second System Option CodeSection [015] Third System Option Code Section [6] ON: the Audible Exit Fault featu

Strany 9

Section 5 – Programming Descriptions15[016] Fourth System Option Code Section [017] Fifth System Option CodeSection [018] Sixth System Option CodeOpti

Strany 10

PowerSeries - PC1616/PC1832/PC186416Section [019] Seventh System Option CodeSection [020] Keypad Zone AssignmentEnter the two-digit zone number to be

Strany 11 - Section 4: Programming

Section 5 – Programming Descriptions17Section [022] Ninth System Option CodeSection [023] Tenth System Option Code Section [030] Fast Loop ResponseTh

Strany 12 - 4.6 DLS Programming

Table of ContentsSection Description Page122.12.22.32.42.52.62.72.82.92.10Product Specifications...

Strany 13

PowerSeries - PC1616/PC1832/PC186418 Keypad zones and zone expanders will always follow Section [013].When Zone Types (Section [00

Strany 14

Section 5 – Programming Descriptions19 Section [169] Standard Time (Set Clock Back)These sections are used to program the Date, Time and Increment tha

Strany 15 - Option Description

PowerSeries - PC1616/PC1832/PC186420Section [301] to [303] Telephone NumbersProgram the phone numbers as required. Phone Number 3 is dedicated as a b

Strany 16 - ][5] command

Section 5 – Programming Descriptions21Section [378] Test Transmission TimeProgram the time the system will report a Test Transmission reporting event.

Strany 17

PowerSeries - PC1616/PC1832/PC186422Section [382] Third Communicator Option CodeSection [383] Fourth Communicator Option CodeSection [389] T-Link Faul

Strany 18

Section 5 – Programming Descriptions23Section [402] Downloading Computer Phone NumberThe Downloading Computer Telephone Number is used for Call Back,

Strany 19 - ][2], [][3] menu access

PowerSeries - PC1616/PC1832/PC186424PGM Output Option [10]PGM Output Option [31]PGM Output Option [32] [3] ON: PGM output activates if a Telephone Lin

Strany 20

Section 5 – Programming Descriptions25PGM Output Option [29] and [35]-[41] Section [551] to [564] PGM Partition AssignmentThese sections are used to c

Strany 21

PowerSeries - PC1616/PC1832/PC186426Section [702] Second International Option CodeSection [703] Delay Between Dialing AttemptsProgram the time the pan

Strany 22 - ] key press

Section 5 – Programming Descriptions27 All template programming information must be re-entered after performing a hardware or software panel default.

Strany 23

Section 1: Product Specifications1Section 1: Product SpecificationsControl and Indicating Equipment SpecificationsZone Configuration• 39 zone types, 1

Strany 24

PowerSeries - PC1616/PC1832/PC186428Section [993] to [999]: Factory Default Module/PanelThe following Sections can be used to factory default a module

Strany 25

Section 5: Programming Work Sheets29Section 5: Programming Work Sheets5.1 Index to Programming Work SheetsProgramming Option Page[000] Keypad Enrollme

Strany 26

PowerSeries - PC1616/PC1832/PC1864305.2 Programming WorksheetsKeypad Partition /Slot and Function Key Programming[000] Keypad Enrollment This must be

Strany 27

5.2 Programming Worksheets31[005] System Times Entry delay shall be no longer then 45 seconds for systems compliant with EN50131-1 and TS50131-3 stan

Strany 28 - Special Installer Functions

PowerSeries - PC1616/PC1832/PC186432Programmable Output Options01 Residential Burglary and Fire Bell Output 18 Stay Armed Status 36 Zone Follower Out

Strany 29

5.2 Programming Worksheets33[013] First System Options[014] Second System Options[015] Third System OptionsProgramming option indicated in GRAY are re

Strany 30

PowerSeries - PC1616/PC1832/PC186434[017] Fifth System Options[018] Sixth System Options[019] Seventh System OptionsKeypad Zone Assignments[020] Keypa

Strany 31 - Programming Option Page

5.2 Programming Worksheets35[021] Eighth System Options Programming option indicated in GRAY are required for systems compliant with EN50131-1 and TS5

Strany 32 - 5.2 Programming Worksheets

PowerSeries - PC1616/PC1832/PC186436[101]-[164] Zone AttributesZone Attribute Defaults (Y = Option ON; N = Option OFF): Attribute: 123456 78ON Audible

Strany 33 - [005] System Times

5.2 Programming Worksheets37Section Zone # Zone Audible/ Steady/ Chime Bypass Force* Swing Tx. Delay Wireless Cross Type** Silent Pulsed No No No No N

Strany 34 - Other System Options

PowerSeries - PC1616/PC1832/PC18642Section 2: Installation & Wiring This Installation Guide provides the basic installation, wiring and programmin

Strany 35

PowerSeries - PC1616/PC1832/PC186438Section Zone # Zone Audible/ Steady/ Chime Bypass Force* Swing Tx. Delay Wireless CrossType** Silent Pulsed No No

Strany 36

5.2 Programming Worksheets39[167] T-LINK Interface Communications Wait for Acknowledge Default 020 I_______I_______I_______I Valid entries are 001-255

Strany 37

PowerSeries - PC1616/PC1832/PC186440No Activity Arming Timers - Default is [000] for all partitionsSection Partition[191] 1 I_______I_______I_______I

Strany 38 - [101]-[164] Zone Attributes

5.2 Programming Worksheets41Communications[304] Call Waiting Cancel String (6 Digits) - This feature is activated in Section 382 Opt 4I_______I_______

Strany 39

PowerSeries - PC1616/PC1832/PC186442[324]-[327] Alarm Restoral Reporting Codes, Zones 01-64 Section[324] Zone 01 Zone 02 Zone 03 Zone 04 Zone 05 Zon

Strany 40 - System Timers

5.2 Programming Worksheets43[334]-[337] Tamper Restoral Reporting Codes, Zones 01-64 Section[334] Zone 01 Zone 02 Zone 03 Zone 04 Zone 05 Zone 06 Z

Strany 41

PowerSeries - PC1616/PC1832/PC186444 [344] Miscellaneous Opening (Disarming) Reporting CodesI_______I_______IFor Future UseI_______I____

Strany 42

5.2 Programming Worksheets45Call Direction Options[351]-[358] Alarm/Restore Communicator Call Directions [359]-[366] Tamper/Restore Communicator Call

Strany 43

PowerSeries - PC1616/PC1832/PC186446[377] Communication VariablesDefault 003 I_______I______I_______I Swinger Shutdown (Alarms and Rest) 001-014 Trans

Strany 44

5.2 Programming Worksheets47[382] Third Communicator Options[383] Fourth Communicator Options[389] T-Link Fault Check Timer Default: 007 I_______I____

Strany 45

Installation32.1 Keybus WiringThe 4-wire KEYBUS (red, black, yellow and green) is the communication connection between the control panel and all modul

Strany 46 -

PowerSeries - PC1616/PC1832/PC186448[501]- [514]Programmable Output Attributes Program only the following attributes for the PGM options listed. All o

Strany 47

5.2 Programming Worksheets49Section PGM Output 1 2 3 4 5

Strany 48

PowerSeries - PC1616/PC1832/PC186450[557] 7 I________I I________| I________| I________| I________| I________| I________| I________I[558] 8 I________I

Strany 49

5.2 Programming Worksheets51[605]-[608] Opening (Disarming) Reporting Codes, Access Codes 33-95Section[605] Code 33 Code 34 Code 35 Code 36 Code 37

Strany 50 - 123456 7 8

PowerSeries - PC1616/PC1832/PC186452[694]Holiday 1 Holiday 2 Holiday 3 Holiday 4 Holiday 5 Holiday 6 Holiday 7I____I_____I I_____I_____I I_____I_____I

Strany 51

5.2 Programming Worksheets53INTERNATIONAL PROGRAMMING[700] Automatic Clock Adjust Default = 60 |________|_________| Valid Entries 00-99 Secon

Strany 52 - Extended Reporting Codes

PowerSeries - PC1616/PC1832/PC186454Special Installer Functions[899] Template Programming[900] Panel Version Displayed[901] InstallerWalk Test Mode En

Strany 53

Appendix A: Reporting CodesAppendix A: Reporting CodesThe following tables contain Contact ID and Automatic SIA format reporting codes. For more info

Strany 54

PowerSeries - PC1616/PC1832/PC1864[345]-[346] Fire Trouble/Rest. Trouble occurs/restores on a fire zone MA/R (3) 73 FT-99/FJ-99[345]-[346] Auxiliary P

Strany 55

Appendix B: Troubleshooting GuideAppendix B: Troubleshooting GuideTesting:• Power up system• Program options as required (See Programming Section)NOT

Strany 56

PowerSeries - PC1616/PC1832/PC18644PC1616/1832/1864 Wiring DiagramCON1 BA T+B AT - 1. Inser t Stand off into cabinet mounting hole in the desired loca

Strany 57 - Appendix A: Reporting Codes

PowerSeries - PC1616/PC1832/PC1864Trouble Cause TroubleshootingTrouble [1] Service Required Press [1] to determine specific tro

Strany 58

Appendix B: Troubleshooting GuideTrouble Cause TroubleshootingTrouble [2] AC FailureNo AC at panel AC input terminalsVerify voltage measured across AC

Strany 59 - Trouble Summary:

PowerSeries - PC1616/PC1832/PC1864Trouble Cause TroubleshootingTrouble [5] Zone Fault (Cont.)One or more wireless devices have not checked in within t

Strany 60 - Trouble Cause Troubleshooting

Appendix C: Template ProgrammingTemplate programming allows quick programming of the minimum functions required for basic operation. The below tables

Strany 61

• Digit 4 selects reporting code configurations Common Group Selected TroublesOptionCommonGroupSelectedTroublesOpenings/ClosingsZoneRestoralsDLS/Insta

Strany 62

Appendix C: Template ProgrammingOpenings & ClosingsZone Restorals DLS/Installer Lead IN/OUT• Digit 5 selects DLS connection options.Users CLOSINGS

Strany 64 - Selected Troubles

PowerSeries - PC1616/PC1832/PC1864Note to InstallersThis warning contains vital information. As the only individual in contact with system users, it i

Strany 65 - DLS/Installer Lead IN/OUT

© 2007, Digital Security ControlsPrinted in Canada . • www.dsc.com29007352R001

Strany 66

Installation52.5 AUX Power WiringThe control panel can provide a maximum of 700mA of current for modules, powered detectors, relays, LED’s etc. If the

Strany 67 - Limited Warranty

PowerSeries - PC1616/PC1832/PC18646Section 3: User CommandsAny system keypad can be used to program or perform any keypad command. LED keypads use st

Strany 68 - 29007352R001

Section 3: User Commands7[][2] Trouble DisplayRefer to Appendix B– Trouble Conditions, for troubleshooting assistance and a detailed description of